Low Voltage Cables/ PVC Insulated Low Voltage Cables/Four Core Cables Cu/PVC/PVC/SWA/PVC & Cu/PVC/SWA/PVC


Four Core Cables Cu/PVC/PVC/SWA/PVC & Cu/PVC/SWA/PVC

600/1000 V - FOUR CORE
COPPER CONDUCTOR
PVC INSULATED STEEL WIRE ARMOURED
PVC SHEATHED CABLES

(CU/PVC/PVC/SWA/PVC AND CU/PVC/SWA/PVC)


Nominal Area of Conductor  Maximum Conductor Resistance  at 20°C   Thickness of Insulation  Thickness of Bedding Diameter of Armour Wire Thickness of Outer Sheath Approx. Overall Diameter. Approx. Cable Weight Standard Packing Length  Drum size  Approx. Gross Weight
Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding
Sqmm Ohm/Km mm mm mm mm mm Kg/Km Metre± 10%    kg
1.5* 12.1 0.8 1.0 - 0.9 1.8 15.7 - 445 - 1000 D-11 545 -
1.5 12.1 0.8 1.0 - 0.9 1.8 16.2 - 470 - 1000 D-11 570 -
2.5* 7.41 0.8 1.0 - 0.9 1.8 16.7 - 510 - 1000 D-11 610 -
2.5 7.41 0.8 1.0 - 0.9 1.8 17.2 - 540 - 1000 D-12 650 -
 
4 4.61 1.0 1.0 - 1.25 1.8 20.1 - 800 - 1000 D-12 910 -
6 3.08 1.0 1.0 - 1.25 1.8 21.5 - 940 - 1000 D-14 1090 -
10 1.83 1.0 1.0 - 1.25 1.8 23.9 - 1200 - 1000 D-14 1350 -
 
16 1.15 1.0 1.0 - 1.6 1.8 27.1 - 1680 - 500 D-14 990 -
25 0.727 1.2 1.0 0.8 1.6 1.8 27.9 26.8 2040 1925 500 D-12 1130 1075
35 0.524 1.2 1.0 0.8 1.6 1.9 31.5 30.4 2550 2440 500 D-14 1430 1370
 
50 0.387 1.4 1.2 0.8 2.0 2.1 36.5 35.0 3530 3330 500 D-16 1980 1875
70 0.268 1.4 1.2 0.8 2.0 2.2 39.6 38.1 4450 4250 500 D-18 2470 2365
95 0.193 1.6 1.2 0.8 2.5 2.4 46.0 44.5 6100 5900 500 D-18 3290 3190
 
120 0.153 1.6 1.4 0.8 2.5 2.5 49.3 47.4 7370 7030 500 D-19 4010 3835
150 0.124 1.8 1.4 0.8 2.5 2.7 53.5 51.9 8760 8380 250 D-18 2430 2335
185 0.0991 2.0 1.6 0.8 2.5 2.9 59.2 56.9 10600 10120 250 D-18 2890 2770
 
240 0.0754 2.2 1.6 0.8 2.5 3.1 64.8 62.5 13100 12645 250 D-18 3520 3400
300 0.0601 2.4 1.6 0.8 2.5 3.3 70.6 68.3 16000 15375 250 D-19 4320 4165
400 0.0470 2.6 1.8 0.8 3.15 3.6 79.7 77.0 20800 20035 200 D-19 5520 4325
 
500 0.0366 2.8 1.8 0.8 3.15 3.9 88.8 86.1 25400 24555 200 D-23 5580 5410

* Circular solid conductor (Class 1).
   Conductor including 16 Sqmm Circular stranded (Class 2).
   25 Sqmm And above shaped stranded conductors (Class 2).
   All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
   Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound. 
   Durm size given above are for Cables with extruded bedding.
   Cables conform to IEC 60502 -1.