Four Core Cables AL/PVC/PVC/SWA/PVC & AL/PVC/SWA/PVC
600/1000 V - FOUR CORE
ALUMINIUM CONDUCTOR
PVC INSULATED STEEL WIRE ARMOURED
PVC SHEATHED CABLES
(AL/PVC/PVC/SWA/PVC AND AL/PVC/SWA/PVC)
Nominal Area of Conductor |
Maximum Conductor Resistance at 20°C |
Thickness of Insulation |
Thickness of Bedding |
Diameter of Armour Wire |
Thickness of Outer Sheath |
Approx. Overall Diameter
|
Approx. Cable Weight |
Standard Packing Length |
Drum size |
Approx. Gross Weight |
Extruded Bedding |
Lapped Bedding |
Extruded Bedding |
Lapped Bedding |
Extruded Bedding |
Lapped Bedding |
Extruded Bedding |
Lapped Bedding |
Sqmm |
Ohm/Km |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Metre± 10% |
|
kg |
25 |
1.20 |
1.2 |
1.0 |
0.8 |
1.6 |
1.8 |
27.9 |
26.8 |
1420 |
1310 |
500 |
D-12 |
820 |
765 |
35 |
0.868 |
1.2 |
1.0 |
0.8 |
1.6 |
1.9 |
31.3 |
30.8 |
1720 |
1580 |
500 |
D-14 |
1010 |
940 |
50 |
0.641 |
1.4 |
1.2 |
0.8 |
2.0 |
2.1 |
36.5 |
35.0 |
2400 |
2190 |
500 |
D-18 |
1440 |
1335 |
|
70 |
0.443 |
1.4 |
1.2 |
0.8 |
2.0 |
2.2 |
39.6 |
38.1 |
2840 |
2620 |
500 |
D-18 |
1660 |
1550 |
95 |
0.320 |
1.6 |
1.2 |
0.8 |
2.5 |
2.4 |
45.7 |
44.2 |
3910 |
3600 |
500 |
D-19 |
2200 |
2040 |
120 |
0.253 |
1.6 |
1.4 |
0.8 |
2.5 |
2.5 |
49.3 |
47.4 |
4470 |
4110 |
500 |
D-19 |
2560 |
2380 |
|
150 |
0.206 |
1.8 |
1.4 |
0.8 |
2.5 |
2.7 |
52.1 |
50.2 |
5050 |
4710 |
500 |
D-19 |
2850 |
2680 |
185 |
0.164 |
2.0 |
1.6 |
0.8 |
2.5 |
2.9 |
59.0 |
56.7 |
6080 |
5650 |
500 |
D-22 |
3510 |
3300 |
240 |
0.125 |
2.2 |
1.6 |
0.8 |
2.5 |
3.1 |
65.0 |
62.7 |
7310 |
6800 |
250 |
D-18 |
2070 |
1940 |
|
300 |
0.100 |
2.4 |
1.6 |
0.8 |
2.5 |
3.3 |
70.6 |
68.3 |
8590 |
8050 |
250 |
D-21 |
2570 |
2430 |
400 |
0.0778 |
2.6 |
1.8 |
0.8 |
3.15 |
3.6 |
79.7 |
77.0 |
11180 |
10810 |
200 |
D-19 |
2560 |
2480 |
500 |
0.0605 |
2.8 |
1.8 |
0.8 |
3.15 |
3.9 |
88.9 |
86.1 |
13690 |
12690 |
200 |
D-21 |
3160 |
2960 |
All conductors shaped stranded (Class 2).
All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.
Drum size given above are for Cables with extruded bedding
Cables conform to IEC 60502 - 1.