Medium Voltage Cables/ XLPE Insulated Medium Voltage Cables/Single Core Cables 6.35/11 KV (CU/SC/XLPE/SC/CUT/PVC)


Single Core Cables 6.35/11 KV (CU/SC/XLPE/SC/CUT/PVC)

6.35/11 KV - SINGLE CORE

(HIGHEST SYSTEM VOLTAGE - 12 KV)

COPPER CONDUCTOR XLPE INSULATED

COPPER TAPE SCREENED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/CUT/PVC/AWA/PVC)


 Area of Conductor


Nominal

DC Conductor
Resistance
at 20°C

Maximum
Conductor
Diameter 
 
Approx

Thickness of XLPE Insulation

Nominal

Thickness
of 
Outer Sheath

Nominal
Overall Diameter

Approx
Cable
Weight

Approx
Standard
Packing Length
Drum
Size
Gross Weight

Approx
Sqmm Ohm/Km mm mm mm mm Kg/Km Metre±5%   Kg
35 0.524 7.1 3.4 1.6 19.6 620 1000 D-12 730
50 0.387 8.2 3.4 1.6 20.7 755 1000 D-12 865
70 0.268 9.8 3.4 1.7 22.5 975 1000 D-14 1125
 
95 0.193 11.4 3.4 1.7 24.1 1240 1000 D-14 1390
120 0.153 12.8 3.4 1.8 25.7 1490 1000 D-16 1700
150 0.124 14.2 3.4 1.8 27.1 1770 1000 D-18 2010
 
185 0.0991 15.9 3.4 1.9 29.0 2150 1000 D-18 2390
240 0.0754 18.5 3.4 2.0 31.8 2710 1000 D-18 2950
300 0.0601 20.6 3.4 2.0 34.0 3335 1000 D-18 3575
 
400 0.0470 23.3 3.4 2.2 37.3 4185 500 D-18 2335
500 0.0366 26.5 3.4 2.2 40.5 5220 500 D-18 2850
 
630 0.0283 30.0 3.4 2.4 44.4 6550 500 D-18 3515
800 0.0221 34.4 3.4 2.5 49.0 8225 500 D-19 4435
1000 0.0176 38.5 3.4 2.6 53.3 10215 500 D-19 5425
All conductors circular compacted.
Equivalant voltage designation as per IEC: 60502 - 2 : 6/10 KV.
Cables conform to IEC 60502 - 2.