Fire Resistant Cable/ Data Tables/0.6/1.0 (1.2) KV, Three-Core Cable, Armoured, Sheathed CU / MGT / XLPE / LSZH / SWA / LSZH


0.6/1.0 (1.2) KV, Three-Core Cable, Armoured, Sheathed CU / MGT / XLPE / LSZH / SWA / LSZH

Description :

Stranded copper conductor, Mica Glass tape & XLPE Insulated, Extruded LSZH bedding, Round galvanized steel wire armoured and LSZH outer sheathed cable.

Core Colour   :  Red, Yellow, Blue    -    Sheath Colour  :  Black 

Standards   :

Construction :  BS 7846.

Testing          :  BS 6387, BS EN / IEC 60754, BS EN / IEC 61034, IEC 60331,  BS EN IEC 60332-3-24.

 

Installation Condition:

   *  In free air or on a perforated cable tray

   *  Ambient Air Temperature : 30°C

   *  Conductor operating Temperature : 90°C

 

  • Conductors including 16 sq.mm circular shaped, 25 sq.mm and above sector shaped (class 2)
  • Cable construction to other standard and other core/sheath colour available upon request.

Cable Size Approx. Conductor Dia./Sect. Height  Nominal Insulation Thickness Approximate Diameter Approx. Cable Weight Standard Packing Length

(± 5%)

 

Maximum Conductor Resistance at 20°C

 

Current Rating in Free Air*
Under Armour Over Armour

Overall

Sqmm  mm mm mm mm mm Kg/Km Meter Ohm/Km A
1.5 1.55 0.6 10.0 11.8 14.4 410 1000 12.1 25
2.5 1.98 0.7 11.3 13.1 15.9 490 1000 7.41 33
4 2.52 0.7 12.6 14.4 17.2 585 1000 4.61 44
6 3.08 0.7 13.7 15.5 18.3 675 1000 3.08 56
10 3.8 0.7 15.4 17.9 20.9 990 1000 1.83 78
16 4.9 0.7 17.8 20.3 23.5 1265 1000 1.15 99
25 4.8 0.9 18.8 22.0 25.4 1640 500 0.727 131
35 5.9 0.9 21.2 24.4 28.0 2020 500 0.524 162
50 7..2 1.0 24.3 27.5 31.1 2515 500 0.387 197
70 8.2 1.1 26.9 30.1 33.9 3230 500 0.268 251
95 10.0 1.1 31.1 35.1 39.3 4445 500 0.193 304
120 11.4 1.2 34.5 38.5 42.9 5370 500 0.153 353
150 12.2 1.4 37.4 42.4 47.0 6790 500 0.124 406
185 13.8 1.6 41.7 46.7 51.5 8055 250 0.0991 463
240 16.3 1.7 47.4 52.4 57.6 10050 250 0.0754 546
300 17.9 1.8 51.6 56.6 62.0 12100 250 0.0601 628
400 20.8 2.0 58.6 63.6 69.4 15040 200 0.0470 728