Current Rating & Voltage Drop

Current rating for voltage drop of cables given below are based on the IEEE wiring regulations 17th edition. For detailed information, reference should be made to Appendix 4 of above IEEE edition.

Current Carrying Capacity(Amps)
Single Core PVC Insulated Non- Sheathed Cables - Cables in conduit on a wall or ceiling or in trunking
Nominal Area of conductor 2 cables single phase ac or dc 3 or 4 cables three phase ac
 sqmm     at 70°C at 85°C  at 70°C   at 85°C 
1        13.5   16   12 14 
   1.5        17.5   21      15.5 18 
   2.5    24  28      21   25 
4    32  38    28 33 
6     41   48     36  42 
 10    57 67   50 59 
16   76  87    68 78 
 25    101   116     89  102 
 35    125   143       110   126 
50   151  173     134  154 
70   192   220      171  196 
95   232   266       207   237 
120    269  309      239   274 
150     300    342       262   298 
185     341   390      296   339 
240     400    458       346   396 
300    458  525      394   452 
400    546   626       467   535 
500    626   712       533   606 
630    720   816       611   693 

Installation Conditions for above Rating:

Maximium Conductor Temp. for PVC Type 5 Insulation                 85°C

Maximium Conductor Temp. for PVC TI1/Type A Insulation           70°C

Ambient Air Temperature                                                           30°C