Two Core Aluminium, PVC Insulated Armoured /Unarmoured Cables
Current Rating & Voltage drop for cables & wires Upto and Including 600/1000V
Two Core Aluminium, PVC Insulated Armoured /Unarmoured Cables
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
Sqmm
|
A |
A |
A |
V/A/Km |
V/A/Km |
16 |
70 |
80 |
73 |
83 |
87 |
97 |
71 |
79 |
4.6 |
4.8 |
25 |
90 |
103 |
92 |
105 |
112 |
125 |
92 |
102 |
2.89 |
3.02 |
35 |
109 |
124 |
112 |
128 |
136 |
151 |
109 |
121 |
2.09 |
2.21 |
50 |
134 |
153 |
136 |
156 |
159 |
177 |
131 |
146 |
1.55 |
1.63 |
70 |
169 |
194 |
174 |
199 |
199 |
222 |
162 |
180 |
1.08 |
1.13 |
95 |
209 |
239 |
213 |
244 |
238 |
265 |
194 |
215 |
0.79 |
0.82 |
120 |
241 |
276 |
241 |
276 |
261 |
291 |
227 |
253 |
0.63 |
0.66 |
150 |
276 |
315 |
276 |
315 |
299 |
332 |
251 |
279 |
0.52 |
0.54 |
185 |
316 |
362 |
316 |
362 |
342 |
380 |
288 |
319 |
0.42 |
0.44 |
240 |
374 |
427 |
374 |
427 |
397 |
441 |
330 |
368 |
0.34 |
0.35 |
300 |
419 |
478 |
419 |
478 |
441 |
489 |
365 |
404 |
0.28 |
0.30 |
400 |
482 |
551 |
482 |
551 |
478 |
531 |
418 |
466 |
0.24 |
0.25 |
Installation conditions for above Rating:
Maximum Conductor Temp. for PVC Type 5 Insulation 85oC
Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC
Ambient Air Temperature 30oC
Ground Temperature 20oC
Depth of Laying 0.5m
Thermal Resitivity of soil 1.2 K.m/w