Two Core Copper, PVC Insulated, Armoured /Unarmoured Cables
Current Rating & Voltage drop for cables & wires Upto and Including 600/1000V
Two Core Copper, PVC Insulated, Armoured /Unarmoured Cables;
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
Sqmm |
A |
A |
A |
V/A/Km |
V/A/Km |
1.5 |
22 |
26 |
22 |
26 |
31 |
35 |
25 |
28 |
30.4 |
30.4 |
2.5 |
31 |
36 |
31 |
36 |
39 |
44 |
32 |
36 |
18.6 |
18.6 |
4 |
41 |
48 |
41 |
48 |
52 |
59 |
43 |
49 |
11.6 |
11.6 |
6 |
52 |
61 |
53 |
62 |
65 |
74 |
55 |
63 |
7.7 |
7.7 |
10 |
67 |
79 |
73 |
86 |
88 |
100 |
73 |
83 |
4.6 |
4.6 |
16 |
91 |
104 |
95 |
109 |
113 |
126 |
93 |
103 |
2.8 |
2.9 |
25 |
122 |
140 |
127 |
145 |
150 |
167 |
123 |
137 |
1.75 |
1.83 |
35 |
150 |
172 |
155 |
177 |
181 |
201 |
146 |
162 |
1.26 |
1.33 |
50 |
182 |
209 |
189 |
217 |
214 |
238 |
174 |
193 |
0.94 |
0.99 |
70 |
228 |
261 |
237 |
271 |
264 |
294 |
214 |
239 |
0.66 |
0.69 |
95 |
283 |
324 |
293 |
336 |
317 |
353 |
258 |
287 |
0.49 |
0.51 |
120 |
329 |
377 |
337 |
386 |
359 |
400 |
294 |
328 |
0.40 |
0.41 |
150 |
377 |
429 |
384 |
437 |
402 |
445 |
330 |
365 |
0.34 |
0.35 |
185 |
435 |
500 |
444 |
510 |
455 |
508 |
374 |
416 |
0.28 |
0.29 |
240 |
518 |
594 |
524 |
601 |
525 |
585 |
433 |
483 |
0.24 |
0.24 |
300 |
596 |
684 |
596 |
684 |
587 |
655 |
486 |
541 |
0.21 |
0.21 |
400 |
693 |
796 |
683 |
784 |
659 |
736 |
546 |
608 |
0.19 |
0.19 |
Installation conditions for above Rating:
Maximum Conductor Temp. for PVC Type 5 Insulation 85oC
Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC
Ambient Air Temperature 30oC
Ground Temperature 20oC
Depth of Laying 0.5m
Thermal Resitivity of soil 1.2 K.m/w