Low Voltage Cables/ PVC Insulated Low Voltage Cables/Four Core Cables with reduced Neutral Cu/PVC/PVC


Four Core Cables with reduced Neutral Cu/PVC/PVC

600/1000 V - FOUR CORE WITH REDUCED NEUTRAL

COPPER CONDUCTOR PVC INSULATED

PVC SHEATHED CABLES

(CU/PVC/PVC)


Nominal Area of Conductor Maximum Conductor Resistance at 20°C  Thickness of Insulations Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross Weight
Phase Neutral Phase Neutral Phase Neutral
Sqmm Ohm/Km mm mm mm Kg/Km Metre ± 10%   Kg
  10* 6 1.83 3.08 1.0 1.0 1.8 18.2 540 1000 D-12 650
  16* 10 1.15 1.83 1.0 1.0 1.8 20.7 760 500 D-10 440
25 16 0.727 1.15 1.2 1.0 1.8 23.3 1140 500 D-11 670
 
35 16 0.524 1.15 1.2 1.0 1.8 26.7 1450 500 D-12 835
50 25 0.387 0.727 1.4 1.2 1.9 30.3 1970 500 D-12 1100
70 35 0.268 0.524 1.4 1.2 2.0 33.4 2690 500 D-16 1560
 
95 50 0.193 0.387 1.6 1.4 2.2 38.8 3670 500 D-18 2080
120 70 0.153 0.268 1.6 1.4 2.3 41.7 4590 500 D-18 2540
150 70 0.124 0.268 1.8 1.4 2.4 46.6 5560 500 D-19 3100
 
185 95 0.0991 0.193 2.0 1.6 2.6 51.5 6940 250 D-18 1980
240 120 0.0754 0.153 2.2 1.6 2.8 57.1 8860 250 D-18 2460
300 150 0.0601 0.124 2.4 1.8 3.0 63.3 11080 250 D-18 2870
 
300 185 0.0601 0.0991 2.4 2.0 3.0 63.3 11370 250 D-18 3080
400 185 0.0470 0.0991 2.6 2.0 3.2 70.5 14110 200 D-19 3140
500 240 0.0366 0.0754 2.8 2.2 3.5 78.7 18300 200 D-21 4080

* Phase conductors upto 16 Sqmm circular stranded (Class 2).
   Phase Conductors 25 Sqmm and above shaped stranded (Class 2).
   All neutral conductors circular stranded (Class 2).
   All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
   Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound. 
   Cables conform to IEC 60502 - 1.