Lead Sheathed Cables/ Current Ratings/1 KV Copper Conductor XLPE Insulated Two core Armoured Cables


1 KV Copper Conductor XLPE Insulated Two core Armoured Cables

LOW VOLTAGE CABLES 600/1000 V

COPPER CONDUCTOR
XLPE INSULATED CABLES

TWO CORE ARMOURED CABLES


CURRENT CARRYING CAPACITY IN AMPERES

Nominal Area of Conductor Sqmm

 

In Air In Ground In Duct
XLPE Insulated XLPE Insulated XLPE Insulated
Copper Copper Copper
 1.5 21 32 26
2.5 28 41 34
4 37 53 44
 
6 47 66 54
10 63 87 72
16 84 113 93
 
25 113 146 120
35 137 174 145
50 165 205 172
 
70 206 251 211
95 254 301 255
120 293 341 290
 
150 332 381 325
185 380 428 367
240 447 494 424
 
300 506 552 475
400 578 619 533
*** l.b.1 ll.b.1 lll.1

Note
***Installation condition(Please refer at the beginning of this section)