Nominal Area of Conductor Maximum Conductor Resistance  at 20°C   Thickness of XLPE Insulation Thickness of Copper Tape Thickness of Extruded Bedding Dia of Armour Wire Thickness of Outer Sheath Approx.  Overall Diameter Approx. Cable Weight Standard Packing Length Drum size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm mm mm mm Kg/Km Metre ± 10%   Kg
50 0.387 8.0 0.075 1.8 3.15 3.4 78.8 9230 500 D-23 5120
70 0.268 8.0 0.075 1.8 3.15 3.5 82.5 10310 500 D-24 5760
95 0.193 8.0 0.075 1.9 3.15 3.6 87.0 11640 500 D-25-S 6570
 
120 0.153 8.0 0.075 2.0 3.15 3.7 90.6 12850 250 D-23 3710
150 0.124 8.0 0.075 2.0 3.15 3.8 93.8 14150 250 D-23 4040
185 0.0991 8.0 0.075 2.1 3.15 4.0 97.9 15700 250 D-23 4430
 
240 0.0754 8.0 0.075 2.2 3.15 4.1 104.0 18120 250 D-25 5280
300 0.0601 8.0 0.075 2.3 3.15 4.3 109.0 20570 200 D-25 4860