Medium Voltage Cables/ XLPE Insulated Medium Voltage Cables/Three Core Cables 12.7/22 KV (Cu/SC/XLPE/SC/CuT/PVC/SWA/PVC)


Three Core Cables 12.7/22 KV (Cu/SC/XLPE/SC/CuT/PVC/SWA/PVC)

12.7/22 KV - THREE CORE

(HIGHEST SYSTEM VOLTAGE - 24 KV)

COPPER CONDUCTOR XLPE INSULATED

COPPER TAPE SCREENED

STEEL WIRE ARMOURED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/CUT/PVC/SWA/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C   Thickness of XLPE Insulation Thickness of Copper Tape Thickness of Extruded Bedding Dia of Armour Wire Thickness of Outer Sheath Approx.  Overall Diameter Approx. Cable Weight Standard Packing Length Drum size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm mm mm mm Kg/Km Metre ± 10%   Kg
35 0.524 5.5 0.075 1.5 2.5 2.8 62.1 5920 500 D-23 3460
50 0.387 5.5 0.075 1.6 2.5 2.9 64.9 6600 500 D-23 3800
70 0.268 5.5 0.075 1.6 2.5 3.1 68.7 7610 500 D-23 4310
 
95 0.193 5.5 0.075 1.7 2.5 3.2 73.2 8870 500 D-23 4940
120 0.153 5.5 0.075 1.7 3.15 3.3 78.0 10730 250 D-21 3100
150 0.124 5.5 0.075 1.8 3.15 3.4 81.4 12000 250 D-23 3500
 
185 0.0991 5.5 0.075 1.9 3.15 3.6 85.5 13460 200 D-22 3160
240 0.0754 5.5 0.075 2.0 3.15 3.7 91.3 15780 200 D-23 3660
300 0.0601 5.5 0.075 2.0 3.15 3.9 96.0 18110 200 D-24 4220
 
400 0.0470 5.5 0.075 2.2 3.15 4.1 103.0 21500 200 D-24 4900

All conductors circular compacted.
Equivalant voltage designation as per IEC: 60502-2 : 12/20 KV.
Cables conform to IEC 60502 - 2.