Medium Voltage Cables/ XLPE Insulated Medium Voltage Cables/Single Core Cables 3.8/6.6 KV (Cu/SC/XLPE/SC/AWA/PVC)


Single Core Cables 3.8/6.6 KV (Cu/SC/XLPE/SC/AWA/PVC)

3.8/6.6 KV - SINGLE CORE

(HIGHEST SYSTEM VOLTAGE - 7.2 KV )

COPPER CONDUCTOR XLPE INSULATED

ALUMINIUM WIRE ARMOURED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/AWA/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C   Thickness of XLPE Insulation Thickness of (Semiconducting) Tape Dia. of Armour Wire Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm mm mm Kg/Km Metre ± 10%   Kg
35 0.524 2.5 0.4 1.6 1.8 23.9 860 500 D-11 530
50 0.387 2.5 0.4 1.6 1.8 25.0 1010 500 D-12 615
70 0.268 2.5 0.4 1.6 1.8 26.6 1250 500 D-12 735
 
95 0.193 2.5 0.4 1.6 1.8 28.5 1560 500 D-12 890
120 0.153 2.5 0.4 1.6 1.9 30.2 1840 500 D-14 1070
150 0.124 2.5 0.4 1.6 1.9 31.6 2160 500 D-14 1230
 
185 0.0991 2.5 0.4 1.6 2.0 33.4 2530 500 D-16 1480
240 0.0754 2.6 0.4 2.0 2.1 37.1 3240 500 D-18 1860
300 0.0601 2.8 0.4 2.0 2.2 39.7 3900 500 D-18 2190
 
400 0.0470 3.0 0.4 2.0 2.3 43.2 4870 500 D-18 2680
500 0.0366 3.2 0.4 2.5 2.4 47.8 6110 500 D-19 3380
630 0.0283 3.2 0.4 2.5 2.5 51.8 7520 500 D-19 4080

All conductors circular compacted
Equivalant voltage designation as per IEC: 60502 - 2 : 3.6/6 KV.
Cables conform to IEC 60502-2.