Multicore Cables For Street Lighting Cu/PVC/PVC
600/1000 V - MULTICORE CABLES
FOR STREET LIGHTING
COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES
(CU/PVC/PVC)
Cable Details |
Nominal Area of Conductor |
Maximum Conductor Resistance at 20°C |
Thickness of Insulation |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
Standard Packing Length |
Drum Size |
Approx. Gross Weight |
Phase |
Neutral & Earth |
Phase |
Neutral & Earth |
Phase |
Neutral & Earth |
|
Sqmm |
Ohm/Km |
mm |
mm |
mm |
Kg/Km |
Metre ±10% |
|
Kg |
2x16+1x10 |
16 |
10 |
1.15 |
1.83 |
1.0 |
1.0 |
1.8 |
19.9 |
735 |
1000 |
D-12 |
830 |
3x25+2x16 |
25 |
16 |
0.727 |
1.15 |
1.2 |
1.0 |
1.8 |
28.3 |
1620 |
500 |
D-12 |
920 |
3x35+2x16 |
35 |
16 |
0.524 |
1.15 |
1.2 |
1.0 |
1.9 |
32.0 |
2070 |
500 |
D-14 |
1190 |
Cable Details |
Nominal Area of Conductor |
Max. Conductor Resistance at 20°C |
Thickness of Insulation |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
Standard Packing Length |
Drum Size |
Approx. Gross Weight |
|
Sqmm |
Ohm/Km |
mm |
mm |
mm |
Kg/Km |
Metre±10% |
|
Kg |
5x1.5* |
1.5 |
12.1 |
0.7 |
1.8 |
12.7 |
230 |
1000 |
D-9 |
290 |
5x1.5 |
1.5 |
12.1 |
0.7 |
1.8 |
13.2 |
240 |
1000 |
D-9 |
300 |
5x2.5* |
2.5 |
7.41 |
0.8 |
1.8 |
13.8 |
290 |
1000 |
D-10 |
350 |
5x2.5 |
2.5 |
7.41 |
0.8 |
1.8 |
14.9 |
325 |
1000 |
D-10 |
385 |
|
5x4 |
4 |
4.61 |
0.8 |
1.8 |
16.2 |
420 |
1000 |
D-11 |
520 |
5x6 |
6 |
3.08 |
0.8 |
1.8 |
17.8 |
545 |
1000 |
D-12 |
655 |
5x10 |
10 |
1.83 |
1.0 |
1.8 |
20.8 |
835 |
500 |
D-10 |
480 |
|
5x16 |
16 |
1.15 |
1.0 |
1.8 |
23.8 |
1170 |
500 |
D-11 |
685 |
5x25 |
25 |
0.727 |
1.2 |
1.9 |
26.2 |
1630 |
500 |
D-12 |
925 |
5x35 |
35 |
0.524 |
1.2 |
2.0 |
31.5 |
2310 |
500 |
D-14 |
1310 |
* Circular solid conductors (Class 1).
All other conductors circular stranded (Class 2).
All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.
Cables conform generally to IEC 60502 - 1.