Low Voltage Cables/ PVC Insulated Low Voltage Cables/Four Core Cables Cu/PVC/PVC


Four Core Cables Cu/PVC/PVC

600/1000 V - FOUR CORE
COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES

(CU/PVC/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C  Thickness of Insulation  Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm Kg/Km Metre ±10%   Kg
1.5* 12.1 0.7 1.8 11.9 200 1000 D-9 260
1.5 12.1 0.7 1.8 12.3 210 1000 D-9 270
2.5* 7.41 0.8 1.8 13.3 265 1000 D-10 325
2.5 7.41 0.8 1.8 13.8 280 1000 D-10 340
 
4 4.61 0.8 1.8 15.0 360 1000 D-10 420
6 3.08 0.8 1.8 16.5 465 1000 D-11 565
10 1.83 1.0 1.8 19.1 690 1000 D-12 800
 
16 1.15 1.0 1.8 21.8 970 500 D-10 545
25 0.727 1.2 1.8 23.3 1290 500 D-11 745
35 0.524 1.2 1.8 26.7 1700 500 D-12 960
 
50 0.387 1.4 1.9 30.3 2310 500 D-14 1310
70 0.268 1.4 2.0 33.4 3130 500 D-16 1780
95 0.193 1.6 2.2 38.8 4260 500 D-18 2370
 
120 0.153 1.6 2.3 41.7 5240 500 D-18 2860
150 0.124 1.8 2.5 46.3 6490 500 D-19 3570
185 0.0991 2.0 2.6 51.0 7980 250 D-18 2240
 
240 0.0754 2.2 2.8 56.6 10230 250 D-18 2800
300 0.0601 2.4 3.1 62.0 12810 250 D-18 3440
400 0.0470 2.6 3.3 69.8 16390 200 D-19 3600
 
500 0.0366 2.8 3.6 78.9 20500 200 D-19 4420

* Circular solid conductor (Class 1).
   Conductors including 16 Sqmm circular stranded (Class 2).
   25 Sqmm and above shaped stranded conductors (Class 2).
   All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
   Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound. 
   Cables upto and including 6 Sqmm generally to BS 6346 and IEC 60502 - 1.
   Cables 10 Sqmm upto and including 400 Sqmm conform generally to BS 6346.
   500 Sqmm Cable conforms to IEC 60502 - 1.