Three/Four Core Aluminium, XLPE Insulated Armoured /Unarmoured Cables
Current Rating And Voltage drop for cables & wires Upto and including 600/1000V
3 & 4 Core Aluminium, XLPE Insulated Armoured /Unarmoured Cables.
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
Sqmm |
A |
A |
A |
V/A/Km |
1.5 |
18 |
18 |
23 |
19 |
- |
2.5 |
24 |
24 |
29 |
25 |
- |
4 |
32 |
32 |
38 |
32 |
16.5 |
6 |
41 |
41 |
49 |
41 |
10.2 |
10 |
55 |
55 |
64 |
53 |
6.8 |
16 |
77 |
77 |
88 |
72 |
4.2 |
25 |
96 |
101 |
113 |
93 |
1.93 |
35 |
118 |
123 |
136 |
110 |
2.70 |
50 |
144 |
149 |
160 |
131 |
1.45 |
70 |
183 |
188 |
198 |
163 |
0.97 |
95 |
226 |
232 |
237 |
195 |
0.72 |
120 |
264 |
270 |
270 |
224 |
0.58 |
150 |
301 |
309 |
302 |
252 |
0.47 |
185 |
350 |
357 |
344 |
286 |
0.39 |
240 |
417 |
422 |
398 |
332 |
0.32 |
300 |
482 |
483 |
447 |
375 |
0.26 |
400 |
562 |
570 |
499 |
412 |
0.21 |
Operating Conditions
Ambient air temperature: 30oC
Ground Temperature: 20oC
Depth of Laying: 0.5 m
Thermal resitivity of soil: 1.2 K.m/W