Current Rating And Voltage drop for cables & wires Upto and including 600/1000V
Single Core Aluminium, PVC Insulated, Armoured /Unarmoured Cables;
Three Single cores in Trefoil touching:
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop of single core cables |
Unarmoured |
Armoured |
Armoured |
Armoured |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
Sqmm |
A |
A |
A |
V/A/Km |
V/A/Km |
16 |
73 |
83 |
73 |
83 |
82 |
91 |
77 |
86 |
3.97 |
4.18 |
25 |
97 |
111 |
97 |
111 |
107 |
119 |
101 |
112 |
2.50 |
2.62 |
35 |
120 |
137 |
120 |
137 |
125 |
139 |
121 |
135 |
1.81 |
1.92 |
50 |
129 |
148 |
132 |
151 |
146 |
163 |
146 |
163 |
1.35 |
1.41 |
70 |
164 |
188 |
167 |
191 |
179 |
199 |
179 |
199 |
0.94 |
0.99 |
95 |
202 |
231 |
204 |
233 |
215 |
239 |
212 |
237 |
0.69 |
0.72 |
120 |
235 |
269 |
238 |
272 |
245 |
273 |
240 |
268 |
0.56 |
0.58 |
150 |
270 |
309 |
272 |
311 |
274 |
305 |
267 |
296 |
0.46 |
0.48 |
185 |
314 |
359 |
316 |
362 |
311 |
346 |
292 |
323 |
0.38 |
0.40 |
240 |
375 |
429 |
374 |
427 |
333 |
370 |
306 |
339 |
0.31 |
0.32 |
300 |
435 |
496 |
430 |
490 |
367 |
407 |
334 |
370 |
0.27 |
0.28 |
400 |
500 |
574 |
500 |
574 |
405 |
452 |
365 |
407 |
0.23 |
0.23 |
500 |
552 |
632 |
552 |
632 |
430 |
479 |
387 |
432 |
0.20 |
0.21 |
630 |
626 |
709 |
626 |
709 |
488 |
538 |
440 |
485 |
0.18 |
0.19 |
800 |
707 |
803 |
707 |
803 |
551 |
608 |
496 |
548 |
0.17 |
0.18 |
1000 |
795 |
894 |
795 |
894 |
619 |
677 |
558 |
610 |
0.16 |
0.17 |
Installation conditions for above Rating:
Maximum Conductor Temp. for PVC Type 5 Insulation 85oC
Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC
Ambient air Temperature 30oC
Ground Temperature 20oC
Depth of Laying 0.5m
Thermal resitivity of soil 1.2 K.m/w