LSZH Cables/ Data Tables/600/1000 V, TWO CORE, ARMOURED CABLES CU / XLPE / LSZH / SWA / LSZH


600/1000 V, TWO CORE, ARMOURED CABLES CU / XLPE / LSZH / SWA / LSZH

Description :

Copper conductor, XLPE Insulated, Extruded LSZH
bedding, Round Steel wire armoured and LSZH outer
sheathed cable.

Color : Red & Black for insulation and Black for sheathing

Standards :
Construction : BS 6724, Generaly comfirm to IEC 60502-1

Testing : BS EN/ IEC 61034, BS EN/ IEC 60754, IEC 60332-3
All conductors circular stranded or circular stranded compacted (class-2)


Conductor Size Max. (DC) Conductor Resistance at 20°C Insulation Thickness Approx. Overall Diameter Current Rating(A.C) Voltage Drop(A.C) Approx. Cable Weight Packing Length(±5%) Drum Size
 Sqmm Ohm/Km mm mm Amp V/A/KM Kg/Km Metre  
1.5 12.1 0.7 13.2 29 31 325 1000 D-10
2.5 7.41 0.7 14.2 39 19 375 1000 D-10
4 4.61 0.7 15.2 52 12 440 1000 D-11
6 3.08 0.7 16.4 66 7.9 520 1000 D-11
10 1.83 0.7 18.0 90 4.7 670 1000 D-12
16 1.15 0.7 20.9 115 2.9 965 1000 D-12
25 0.727 0.9 24.3 152 1.9 1310 1000 D-14
35 0.524 0.9 27.8 188 1.35 1810 1000 D-18
50 0.387 1.0 30.9 228 1 2070 500 D-14
70 0.268 1.1 34.7 291 0.69 2650 500 D-16
95 0.193 1.1 39.9 354 0.52 3640 500 D-18
120 0.153 1.2 43.5 410 0.42 4330 500 D-18
150 0.124 1.4 47.3 472 0.35 5140 500 D-19
185 0.0991 1.6 53.1 539 0.29 6570 250 D-18
240 0.0754 1.7 58.7 636 0.24 8050 250 D-18
300 0.0601 1.8 63.7 732 0.21 9610 250 D-18
400 0.047 2 70.7 847 0.19 11900 250 D-21

Installation Condition:
Single phase, In free air or on a perforated cable tray

Ambient Air Temperature : 30°C
Conductor operating Temperature : 90°C