Low Voltage Cables/ XLPE Insulated Low Voltage Cables/Two Core Cables Cu/XLPE/PVC


Two Core Cables Cu/XLPE/PVC

600/1000 V - TWO CORE

Copper Conductor XLPE Insulated

PVC Sheathed Cables

(Cu/XLPE/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C  Thickness of Insulation  Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm Kg/Km Metre ±10%   Kg
  1.5* 12.1 0.7 1.8 10.8 150 1000 D-8 200
1.5 12.1 0.7 1.8 11.2 170 1000 D-9 230
  2.5* 7.41 0.7 1.8 11.6 180 1000 D-9 240
2.5 7.41 0.7 1.8 12.0 190 1000 D-9 250
 
4 4.61 0.7 1.8 13.0 240 1000 D-9 300
6 3.08 0.7 1.8 14.2 300 1000 D-10 360
10 1.83 0.7 1.8 15.6 405 1000 D-11 505
 
16 1.15 0.7 1.8 17.8 565 1000 D-12 675
25 0.727 0.9 1.8 21.0 825 500 D-11 515
35 0.524 0.9 1.8 23.2 1070 500 D-12 645
 
50 0.387 1.0 1.8 26.3 1240 500 D-12 730
70 0.268 1.1 1.8 29.3 1700 500 D-12 960
95 0.193 1.1 1.9 33.9 2280 500 D-16 1350
 
120 0.153 1.2 2.0 37.5 2830 500 D-18 1660
150 0.124 1.4 2.2 41.5 3510 500 D-18 2000
185 0.0991 1.6 2.3 45.7 4280 500 D-19 2460
 
240 0.0754 1.7 2.5 51.5 5520 250 D-18 1620
300 0.0601 1.8 2.6 56.1 6810 250 D-18 1940
400 0.0470 2.0 2.9 63.3 8770 250 D-18 2430

* Circular solid conductor (Class 1).

   All other conductors circular stranded or circular stranded compacted (Class 2).

   Cables conform generally to BS 5467 and IEC 60502 - 1.