Two Core Aluminium, XLPE insulated Armoured / Unarmoured cables
Current Rating And Voltage drop for cables & wires Upto and including 600/1000V
Two Core Aluminium, XLPE insulated Armoured / Unarmoured cables:
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
Sqmm |
A |
A |
A |
V/A/Km |
1.5 |
22 |
22 |
25 |
21 |
- |
2.5 |
29 |
29 |
35 |
28 |
- |
4 |
37 |
37 |
44 |
63 |
19.0 |
6 |
48 |
48 |
55 |
46 |
11.8 |
10 |
65 |
65 |
76 |
61 |
7.9 |
16 |
98 |
89 |
105 |
86 |
4.8 |
25 |
110 |
110 |
134 |
108 |
3.10 |
35 |
135 |
135 |
160 |
131 |
2.23 |
50 |
163 |
163 |
191 |
156 |
1.65 |
70 |
209 |
209 |
234 |
191 |
1.15 |
95 |
257 |
257 |
280 |
231 |
0.84 |
120 |
287 |
287 |
301 |
262 |
0.67 |
150 |
328 |
328 |
344 |
289 |
0.55 |
185 |
376 |
376 |
394 |
331 |
0.45 |
240 |
444 |
444 |
459 |
380 |
0.35 |
300 |
499 |
499 |
509 |
420 |
0.30 |
400 |
573 |
573 |
556 |
480 |
0.25 |
Operating Conditions
Ambient Air temperature: 30°C
Ground Temperature: 20°C
Depth of Laying: 0.5 m
Thermal Resitivity of soil: 1.2 K.m/W