Single Core Aluminium, XLPE insulated Armoured / Unarmoured cables.
Current Rating And Voltage drop for cables & wires Upto and including 600/1000V
Single core Aluminium, XLPE insulated Armoured / Unarmoured cables
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop of 3 single core cables Trefoil |
Single core in Trefoil |
Single core Trefoil |
Single core Trefoil |
Unarmoured |
Armoured |
Armoured |
Armoured |
Sqmm |
A |
A |
A |
V/A/Km |
4 |
37 |
37 |
44 |
42 |
16.5 |
6 |
48 |
48 |
55 |
51 |
10.2 |
10 |
65 |
65 |
73 |
70 |
6.8 |
16 |
88 |
88 |
95 |
89 |
4.2 |
25 |
115 |
115 |
123 |
116 |
2.70 |
35 |
144 |
144 |
144 |
139 |
1.93 |
50 |
157 |
165 |
172 |
173 |
1.44 |
70 |
201 |
210 |
211 |
210 |
1.0 |
95 |
249 |
257 |
253 |
247 |
0.73 |
120 |
289 |
299 |
288 |
280 |
0.59 |
150 |
334 |
344 |
322 |
306 |
0.49 |
185 |
389 |
397 |
364 |
340 |
0.40 |
240 |
465 |
470 |
420 |
385 |
0.32 |
300 |
539 |
538 |
472 |
426 |
0.27 |
400 |
594 |
594 |
534 |
481 |
0.25 |
500 |
656 |
656 |
606 |
546 |
0.21 |
630 |
744 |
744 |
688 |
620 |
0.19 |
800 |
842 |
842 |
779 |
703 |
0.18 |
1000 |
946 |
946 |
872 |
788 |
0.17 |
Operating Conditions
Ambient Air temperature: 30oC
Ground Temperature: 20oC
Depth of Laying: 0.5 m
Thermal Resitivity of soil: 1.2 K.m/W