Group Rating Factors single core cables
Group rating factors for circuits of three single core cables in Trefoil and laid flat touching, horizontal formation (average value)
|
Number Of Circuits |
 |
Spacing of Circuits |
Touching |
|
|
Trefoil |
Laid flat |
0.15m* |
0.30m |
0.45m |
0.60m |
|
2 |
0.78 |
0.81 |
0.81 |
0.85 |
0.88 |
0.90 |
|
3 |
0.66 |
0.68 |
0.71 |
0.76 |
0.80 |
0.83 |
12/20kV |
4 |
0.59 |
0.62 |
0.65 |
0.72 |
0.76 |
0.80 |
|
5 |
0.55 |
0.58 |
0.61 |
0.68 |
0.73 |
0.77 |
|
6 |
0.52 |
0.55 |
0.58 |
0.66 |
0.72 |
0.76 |
|
|
2 |
0.79 |
0.81 |
0.81 |
0.85 |
0.88 |
0.90 |
18/30kV |
3 |
0.67 |
0.70 |
0.71 |
0.76 |
0.80 |
0.83 |
|
4 |
0.62 |
0.65 |
0.65 |
0.72 |
0.76 |
0.80 |
|
5 |
0.57 |
0.60 |
0.60 |
0.68 |
0.73 |
0.77 |
|
6 |
0.54 |
0.57 |
0.57 |
0.66 |
0.72 |
0.76 |
*This configuration, at 0.15m spacing, may not be practical for the larger size cables