Four Core Cables Cu/PVC/PVC
600/1000 V - FOUR CORE
COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES
(CU/PVC/PVC)
Nominal Area of Conductor |
Maximum Conductor Resistance at 20°C |
Thickness of Insulation |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
Standard Packing Length |
Drum Size |
Approx. Gross Weight |
Sqmm |
Ohm/Km |
mm |
mm |
mm |
Kg/Km |
Metre ±10% |
|
Kg |
1.5* |
12.1 |
0.7 |
1.8 |
11.9 |
200 |
1000 |
D-9 |
260 |
1.5 |
12.1 |
0.7 |
1.8 |
12.3 |
210 |
1000 |
D-9 |
270 |
2.5* |
7.41 |
0.8 |
1.8 |
13.3 |
265 |
1000 |
D-10 |
325 |
2.5 |
7.41 |
0.8 |
1.8 |
13.8 |
280 |
1000 |
D-10 |
340 |
|
4 |
4.61 |
0.8 |
1.8 |
15.0 |
360 |
1000 |
D-10 |
420 |
6 |
3.08 |
0.8 |
1.8 |
16.5 |
465 |
1000 |
D-11 |
565 |
10 |
1.83 |
1.0 |
1.8 |
19.1 |
690 |
1000 |
D-12 |
800 |
|
16 |
1.15 |
1.0 |
1.8 |
21.8 |
970 |
500 |
D-10 |
545 |
25 |
0.727 |
1.2 |
1.8 |
23.3 |
1290 |
500 |
D-11 |
745 |
35 |
0.524 |
1.2 |
1.8 |
26.7 |
1700 |
500 |
D-12 |
960 |
|
50 |
0.387 |
1.4 |
1.9 |
30.3 |
2310 |
500 |
D-14 |
1310 |
70 |
0.268 |
1.4 |
2.0 |
33.4 |
3130 |
500 |
D-16 |
1780 |
95 |
0.193 |
1.6 |
2.2 |
38.8 |
4260 |
500 |
D-18 |
2370 |
|
120 |
0.153 |
1.6 |
2.3 |
41.7 |
5240 |
500 |
D-18 |
2860 |
150 |
0.124 |
1.8 |
2.5 |
46.3 |
6490 |
500 |
D-19 |
3570 |
185 |
0.0991 |
2.0 |
2.6 |
51.0 |
7980 |
250 |
D-18 |
2240 |
|
240 |
0.0754 |
2.2 |
2.8 |
56.6 |
10230 |
250 |
D-18 |
2800 |
300 |
0.0601 |
2.4 |
3.1 |
62.0 |
12810 |
250 |
D-18 |
3440 |
400 |
0.0470 |
2.6 |
3.3 |
69.8 |
16390 |
200 |
D-19 |
3600 |
|
500 |
0.0366 |
2.8 |
3.6 |
78.9 |
20500 |
200 |
D-19 |
4420 |
* Circular solid conductor (Class 1).
Conductors including 16 Sqmm circular stranded (Class 2).
25 Sqmm and above shaped stranded conductors (Class 2).
All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.
Cables upto and including 6 Sqmm generally to BS 6346 and IEC 60502 - 1.
Cables 10 Sqmm upto and including 400 Sqmm conform generally to BS 6346.
500 Sqmm Cable conforms to IEC 60502 - 1.