Low Voltage Cables/ PVC Insulated Low Voltage Cables/Four Core Cables Cu/PVC/PVC/SWA/PVC & Cu/PVC/SWA/PVC


Four Core Cables Cu/PVC/PVC/SWA/PVC & Cu/PVC/SWA/PVC

600/1000 V - FOUR CORE
COPPER CONDUCTOR
PVC INSULATED STEEL WIRE ARMOURED
PVC SHEATHED CABLES

(CU/PVC/PVC/SWA/PVC AND CU/PVC/SWA/PVC)


Nominal Area of Conductor  Maximum Conductor Resistance  at 20°C   Thickness of Insulation  Thickness of Bedding Diameter of Armour Wire Thickness of Outer Sheath Approx. Overall Dia. Approx. Cable Weight Standard Packing Length  Drum size  Approx. Gross Weight
Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding
Sqmm Ohm/Km mm mm mm mm mm Kg/Km Metre± 10%    kg
1.5* 12.1 0.7 0.8 - 0.9 1.4 14.1 - 385 - 1000 D-10 445 -
1.5 12.1 0.7 0.8 - 0.9 1.4 14.5 - 400 - 1000 D-10 460 -
2.5* 7.41 0.8 0.8 - 0.9 1.4 15.5 - 470 - 1000 D-11 570 -
2.5 7.41 0.8 0.8 - 0.9 1.4 16.0 - 495 - 1000 D-11 595 -
 
4 4.61 0.8 0.8 - 1.25 1.5 18.1 - 700 - 1000 D-12 810 -
6 3.08 0.8 0.8 - 1.25 1.5 19.6 - 830 - 1000 D-12 940 -
10 1.83 1.0 0.8 - 1.25 1.6 22.4 - 1130 - 1000 D-14 1280 -
 
16 1.15 1.0 1.0 - 1.6 1.7 26.4 - 1650 - 500 D-12 935 -
25 0.727 1.2 1.0 0.8 1.6 1.8 27.9 26.8 2040 1890 500 D-12 1130 1060
35 0.524 1.2 1.0 0.8 1.6 1.9 31.5 30.4 2550 2400 500 D-14 1430 1350
 
50 0.387 1.4 1.2 0.8 2.0 2.0 36.3 34.8 3510 3300 500 D-16 1970 1860
70 0.268 1.4 1.2 0.8 2.0 2.1 39.4 37.9 4450 4220 500 D-18 2470 2350
95 0.193 1.6 1.2 0.8 2.0 2.2 44.6 43.1 5770 5510 500 D-18 3130 3000
 
120 0.153 1.6 1.4 0.8 2.5 2.4 49.1 47.2 7350 6970 500 D-19 4000 3810
150 0.124 1.8 1.4 0.8 2.5 2.5 53.5 51.6 8760 8390 250 D-18 2430 2340
185 0.0991 2.0 1.4 0.8 2.5 2.6 58.6 56.3 10530 10040 250 D-18 2870 2750
 
240 0.0754 2.2 1.6 0.8 2.5 2.8 64.2 61.9 13050 12520 250 D-18 3500 3370
300 0.0601 2.4 1.6 0.8 2.5 3.0 70.0 67.7 15880 15300 250 D-19 4290 4150
400 0.0470 2.6 1.8 0.8 3.15 3.3 79.1 76.4 20710 20000 200 D-19 4460 4320
 
500 0.0366 2.8 1.8 0.8 3.15 3.9 88.8 86.1 25400 24720 200 D-23 5580 5440

* Circular solid conductor (Class 1).
   Conductor including 16 Sqmm Circular stranded (Class 2).
   25 Sqmm And above shaped stranded conductors (Class 2).
   All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
   Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound. 
   Durm size given above are for Cables with extruded bedding.
   Cables upto and including 400 Sqmm conform to BS 6346.
   500 Sqmm Cable conforms to IEC 60502 - 1.