Low Voltage Cables/ PVC Insulated Auxilary Cables (Control Cables)/2.5 Sqmm Cables Cu/PVC/PVC/SWA/PVC


2.5 Sqmm Cables Cu/PVC/PVC/SWA/PVC

600/1000 V - AUXILIARY CABLES (CONTROL CABLES)

Copper Conductor

PVC Insulated Steel Wire Armoured

PVC Sheathed Cables

(Cu/PVC/PVC/SWA/PVC) SIZE : 2.5 SQMM


Number of Cores Maximum Conductor Resistance  at 20°C   Thickness of Insulation  Thickness of Extruded Bedding Dia. of Armour Wire Thickness of Outer Sheath Approximate Overall Diameter. Approximate Cable Weight. Standard Packing Length Drum size  Approximate Gross Weight.
No. Ohm/Km mm mm mm mm mm Kg/Km Metre± 10%    kg
2** 7.41 0.7 0.8 0.9 1.4 14.0 370 1000 D-10 430
3** 7.41 0.7 0.8 0.9 1.4 14.6 415 1000 D-10 475
4** 7.41 0.7 0.8 0.9 1.4 15.5 470 1000 D-11 570
 
5** 7.41 0.7 0.8 0.9 1.5 16.7 545 1000 D-11 645
     7 7.41 0.7 0.8 1.25 1.5 18.5 720 1000 D-12 830
8** 7.41 0.7 0.8 1.25 1.5 19.6 815 1000 D-12 925
 
12 7.41 0.7 0.8 1.25 1.6 22.9 1050 500 D-11 625
19 7.41 0.7 1.0 1.6 1.7 27.2 1550 500 D-12 885
27 7.41 0.7 1.0 1.6 1.8 31.6 2010 500 D-14 1160
 
37 7.41 0.7 1.0 1.6 1.9 34.8 2460 500 D-16 1440
48 7.41 0.7 1.2 2.0 2.1 40.6 3330 500 D-18 1910
    61** 7.41 0.7 1.2 2.0 2.2 43.8 3910 500 D-18 2200
 
   91** 7.41 0.7 1.4 2.5 2.5 53.0 5790 500 D-19 3220

     All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C Compound and sheathed with PVC
     Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC Type ST1/TM1 compound.
** Cables conform generally to BS 6346 and IEC 60502 - 1.
     All other cables conform to BS 6346 .
     All conductors circular starnded, cables with solid or flexible conductor available on request.
     Core identification by number printing on white cores.