Voltage Drop at maximum conductor operating temperature in V/A/KM
Conductor Size |
1 Core unarmoured cables
|
1 Core Armoured (Trefoil) |
2 Core Unarmoured & Armoured
|
3 & 4 Un- armoured
& Armoured
|
Sq. mm |
1 Ph(A) |
3 Ph(B) |
1 Ph(C) |
3 Ph(D) |
3 Ph |
1 Ph |
3 Ph |
1.5 |
31 |
27 |
31 |
27 |
27 |
31 |
27 |
2.5 |
19 |
16 |
19 |
16 |
16 |
19 |
16 |
4 |
12 |
10 |
12 |
10 |
10 |
12 |
10 |
6 |
7.9 |
6.8 |
7.9 |
6.8 |
6.8 |
7.9 |
6.8 |
10 |
4.7 |
4.0 |
4.7 |
4.0 |
4 |
4.7 |
4.0 |
16 |
2.9 |
2.5 |
2.9 |
2.5 |
2.5 |
2.9 |
2.5 |
25 |
1.90 |
1.65 |
1.85 |
1.60 |
1.60 |
1.90 |
1.65 |
35 |
1.35 |
1.15 |
1.35 |
1.15 |
1.15 |
1.35 |
1.15 |
50 |
1.05 |
0.90 |
1.00 |
0.87 |
0.87 |
1.00 |
0.87 |
70 |
0.75 |
0.65 |
0.71 |
0.61 |
0.62 |
0.69 |
0.6 |
95 |
0.58 |
0.50 |
0.52 |
0.45 |
0.47 |
0.52 |
0.45 |
120 |
0.48 |
0.42 |
0.43 |
0.37 |
0.39 |
0.42 |
0.37 |
150 |
0.43 |
0.37 |
0.36 |
0.31 |
0.33 |
0.35 |
0.30 |
185 |
0.37 |
0.32 |
0.307 |
0.26 |
0.28 |
0.29 |
0.26 |
240 |
0.33 |
0.29 |
0.25 |
0.22 |
0.24 |
0.24 |
0.21 |
300 |
0.31 |
0.27 |
0.22 |
0.195 |
0.21 |
0.21 |
0.185 |
400 |
0.29 |
0.25 |
0.20 |
0.175 |
0.20 |
0.190 |
0.165 |
500 |
0.28 |
0.24 |
0.185 |
0.160 |
0.18 |
- |
- |
630 |
0.27 |
0.23 |
0.175 |
0.150 |
0.17 |
- |
- |
A -----> 2 cables, enclosed in Conduit or trunking
B -----> 3 or 4 cables , enclosed in Conduit or trunking.
C -----> 2 cables, clipped direct, on tray or in free air (Cable Touching)
D -----> 3 or 4 cables, clipped direct, on tray or in free air (Cable Touching, trefoil)
If you have any queries or comments, please fill in the form below and we will get back to you as soon as possible.