Medium Voltage Cables/ XLPE Insulated Medium Voltage Cables/Single Core Cables 19/33 KV (CU/SC/XLPE/SC/CUT/PVC)


Single Core Cables 19/33 KV (CU/SC/XLPE/SC/CUT/PVC)

19/33 KV - THREE CORE

(HIGHEST SYSTEM VOLTAGE - 36 KV)

COPPER CONDUCTOR XLPE INSULATED 

COPPER TAPE SCREENED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/CUT/PVC)


 Area of Conductor



Nominal

DC Conductor
Resistance
at 20°C

Maximum
Conductor
Diameter 

 
Approx

Thickness of
XLPE
Insulation

Nominal

Thickness
of 
Outer Sheath

Nominal
Overall Diameter


Approx
Cable
Weight


Approx
Standard
Packing Length
Drum
Size
Gross Weight


Approx
Sqmm Ohm/Km mm mm mm mm Kg/Km Metre±5%   Kg
50 0.387 8.2 8.0 1.9 30.5 1165 1000 D-18 1405
70 0.268 9.8 8.0 2.0 32.3 1420 1000 D-18 1660
95 0.193 11.4 8.0 2.1 34.1 1720 1000 D-19 2040
 
120 0.153 12.8 8.0 2.1 35.5 1980 1000 D-19 2300
150 0.124 14.2 8.0 2.2 37.2 2320 500 D-18 1400
185 0.0991 15.9 8.0 2.2 38.9 2715 500 D-18 1595
 
240 0.0754 18.5 8.0 2.3 41.7 3320 500 D-18 1900
300 0.0601 20.6 8.0 2.4 44.0 3970 500 D-18 2225
400 0.0470 23.3 8.0 2.5 47.1 4855 500 D-19 2750
 
500 0.0366 26.5 8.0 2.6 50.5 5955 500 D-19 3300
630 0.0283 30.0 8.0 2.7 54.2 7325 250 D-18 2070
800 0.0221 34.4 8.0 2.8 58.8 9070 250 D-18 2510
 
1000 0.0176 38.5 8.0 2.9 63.1 11120 250 D-18 3020

All conductors circular compacted.
Equivalant voltage designation as per IEC 60502 - 2 : 18/30 KV.
Cables conform to IEC 60502 - 2.