Medium Voltage Cables/ XLPE Insulated Medium Voltage Cables/Three Core Cables 19/33 KV (CU/SC/XLPE/SC/CUT/PVC/SWA/PVC)


Three Core Cables 19/33 KV (CU/SC/XLPE/SC/CUT/PVC/SWA/PVC)

19/33 KV - THREE CORE

(HIGHEST SYSTEM VOLTAGE - 36 KV)

COPPER CONDUCTOR XLPE INSULATED

COPPER TAPE SCREENED

STEEL WIRE ARMOURED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/CUT/PVC/SWA/PVC)


 Area of Conductor



Nominal

DC Conductor
Resistance
at 20°C

Maximum
Conductor
Diameter 

 
Approx

Thickness of
XLPE
Insulation

Nominal

Thickness of
Extruded
Bedding

Nominal

Dia of Armour
Wire

Nominal
Thickness
of 
Outer Sheath

Nominal
Overall Diameter


Approx
Cable
Weight


Approx
Standard
Packing Length
Drum
Size
Gross Weight


Approx
Sqmm Ohm/Km mm mm mm mm mm mm Kg/Km Metre±5%   Kg
50 0.387 8.2 8.0 1.8 3.15 3.4 74.7 8320 500 D-23 4660
70 0.268 9.8 8.0 1.8 3.15 3.5 78.3 9320 500 D-23 5160
95 0.193 11.4 8.0 1.9 3.15 3.6 82.2 10610 500 D-24 5905
 
120 0.153 12.8 8.0 2.0 3.15 3.7 85.6 11675 250 D-23 3420
150 0.124 14.2 8.0 2.0 3.15 3.9 89.2 13015 250 D-23 3755
185 0.0991 15.9 8.0 2.1 3.15 4.0 93.3 14595 250 D-23 4150
 
240 0.0754 18.5 8.0 2.2 3.15 4.2 99.5 17000 250 D-23 4750
300 0.0601 20.6 8.0 2.3 3.15 4.3 104.5 19470 250 D-25 5615

All conductors circular compacted.
Equivalant voltage designation as per IEC 60502 - 2 : 18/30 KV.
Cables conform to IEC 60502 - 2.