Rating factors for variation in Thermal Resistivity of Soil for Twin or Multi-core Cables Laid in Single Way Ducts:
|
Nominal Area of Conductor mm²
|
Thermal Resistivity of Soil in K.m/W |
| |
0.7 |
0.8 |
0.9 |
1.0 |
1.2 |
1.5 |
2.0 |
2.5 |
3.0 |
3.5 |
4.0 |
| 1.5/2.5 |
1.04 |
1.03 |
1.02 |
1.02 |
1.0 |
0.98 |
0.94 |
0.91 |
0.88 |
0.86 |
0.83 |
| 4 |
1.04 |
1.04 |
1.03 |
1.02 |
1.0 |
0.97 |
0.94 |
0.90 |
0.87 |
0.85 |
0.82 |
| 6 |
1.05 |
1.04 |
1.03 |
1.02 |
1.0 |
0.97 |
0.93 |
0.90 |
0.86 |
0.84 |
0.81 |
| 10 |
1.05 |
1.04 |
1.03 |
1.02 |
1.0 |
0.97 |
0.93 |
0.89 |
0.86 |
0.83 |
0.80 |
| 16 |
1.06 |
1.04 |
1.03 |
1.02 |
1.0 |
0.97 |
0.92 |
0.88 |
0.85 |
0.82 |
0.79 |
| 25 |
1.06 |
1.05 |
1.03 |
1.02 |
1.0 |
0.96 |
0.92 |
0.88 |
0.84 |
0.82 |
0.78 |
| 35 |
1.06 |
1.05 |
1.03 |
1.02 |
1.0 |
0.96 |
0.92 |
0.87 |
0.83 |
0.81 |
0.77 |
| 50 |
1.07 |
1.05 |
1.03 |
1.02 |
1.0 |
0.96 |
0.91 |
0.87 |
0.83 |
0.80 |
0.77 |
| 70 |
1.07 |
1.05 |
1.04 |
1.02 |
1.0 |
0.96 |
0.91 |
0.86 |
0.82 |
0.79 |
0.76 |
| 95 |
1.07 |
1.05 |
1.04 |
1.02 |
1.0 |
0.96 |
0.91 |
0.86 |
0.82 |
0.79 |
0.76 |
| 120 |
1.08 |
1.06 |
1.04 |
1.03 |
1.0 |
0.95 |
0.90 |
0.85 |
0.81 |
0.78 |
0.74 |
| 150 |
1.09 |
1.06 |
1.04 |
1.03 |
1.0 |
0.95 |
0.90 |
0.85 |
0.80 |
0.77 |
0.73 |
| 185 |
1.09 |
1.07 |
1.05 |
1.03 |
1.0 |
0.95 |
0.89 |
0.84 |
0.80 |
0.76 |
0.72 |
| 240 |
1.09 |
1.07 |
1.05 |
1.03 |
1.0 |
0.95 |
0.88 |
0.83 |
0.79 |
0.75 |
0.71 |
| 300 |
1.10 |
1.07 |
1.05 |
1.03 |
1.0 |
0.95 |
0.88 |
0.83 |
0.78 |
0.75 |
0.71 |
| 400 |
1.10 |
1.07 |
1.05 |
1.03 |
1.0 |
0.95 |
0.88 |
0.83 |
0.78 |
0.75 |
0.71 |