We build cables for life 15
RATING FACTORS FOR VARIATION IN THERMAL RESISTIVITY OF SOIL
TWIN OR MULTI-CORE CABLES LAID DIRECT IN THE GROUND
Nominal Area of Conductor Sqmm Thermal Resistivity of Soil in °C m/w
0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
1.5/2.5 1.12 1.09 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
4 1.13 1.10 1.07 1.05 1.0 0.94 0.85 0.79 0.74 0.69 0.65
6 1.14 1.10 1.07 1.05 1.0 0.93 0.85 0.79 0.74 0.68 0.64
 
10 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.67 0.63
16 1.16 1.12 1.08 1.05 1.0 0.93 0.84 0.77 0.72 0.66 0.62
25 1.17 1.13 1.09 1.05 1.0 0.93 0.83 0.77 0.71 0.65 0.61
 
35 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
50 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
70 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
 
95 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
120 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.60
150 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
 
185 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.74 0.69 0.63 0.59
240 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
300/400 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59