Lead Sheathed Cables/XLPE Insulated 600/1000V Cables/Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC


Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

600 / 1000 V- FOUR CORE

COPPER CONDUCTOR XLPE INSULATED
LEAD SHEATHED
STEEL WIRE ARMOURED
PVC SHEATHED CABLES
CU/XLPE/PVC/LC/PVC/SWA/PVC


Nominal Area of Conductor Maximum Conductor Resistance at 20°C

Thickness of Insulation(Nom.)

Thickness of SBedding(Approx.) Thickness of Lead Sheath(Nom.) Thickness of Seperation Sheath(Nom.) Dia of Armour wire(Nom.) Thickness of Outer Sheath(Nom.)  Approx. Overall Diameter  Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross weight
 Sqmm Ohm/KM mm mm mm mm mm mm  mm Kg/Km Metre±5%      kg 
 1.5 12.1 0.7 1.0 1.2 1.0 1.25 1.8 21.7 1305 1000 D-14 1455
 2.5 7.41 0.7 1.0 1.2 1.0 1.25 1.8 22.7 1430 1000 D-14 1580
4 4.61 0.7 1.0 1.2 1.0 1.25 1.8 23.9 1605 1000 D-14 1755
 
3.08 0.7 1.0 1.2 1.0 1.60 1.8 26.0 1945 1000 D-16 2155
10 1.83 0.7 1.0 1.2 1.0 1.60 1.8 27.7 2270 1000 D-18 2510
16 1.15 0.7 1.0 1.2 1.0 1.60 1.8 30.4 2760 1000 D-18 3000
 
 25 0.727 0.9 1.0 1.2 1.0 1.60 1.9 31.8 3145 500 D-14 1725
35 0.524 0.9 1.0 1.2 1.1 2.00 2.1 36.6 4080 500 D-18 2280
50 0.387 1.0 1.0 1.4 1.2 2.00 2.2 40.3 2660 500 D-18 2795
 
70  0.268 1.1 1.2 1.5 1.2 2.00 2.3 44.4 6450 500 D-19 3545
95 0.193 1.1 1.2 1.6 1.3 2.50 2.5 50.3 8460 500 D-19 4550
120 0.153 1.2 1.4 1.7 1.4 2.50 2.7 54.7 10100 500 D-23 5550
 
150 0.124 1.4 1.4 1.8 1.5 2.50 2.9 59.5 11960 250 D-18 3230
185 0.0991 1.6 1.4 2.0 1.6 2.50 3.0 65.5 14440 250 D-19 3930
240 0.0754 1.7 1.6 2.2 1.7 2.50 3.3 71.8 17800 250 D-23 4950
 
300 0.0601 1.8 1.6 2.3 1.8 3.15 3.5 79.3 22000 250 D-23 6000
400 0.0470 2.0 1.8 2.6 2.0 3.15 3.8 88.1 27435 200 D-23 5990
500 0.0366 2.2 1.8 2.8 2.2 3.15 4.1 98.0 33475 200 D-23 7195

Conductors including 16 Sqmm Circular Stranded (Class 2).
25 Sqmm and above shaped stranded conductors (Class 2).
Extruded PVC Bedding above and below Lead Sheath.
Lead Alloy Type - 'E' to BS 801, Lead Sheath Thickness to IEC 60502-1/1997.
PVC Type - 9/ST-2 Outersheath.
Cables conform to IEC 60502-1/1997.