Fire Resistant Cable/Data Tables/0.6/1.0 (1.2) KV, Single Core Cable, Armoured, Sheathed CU / MGT / XLPE / LSZH / AWA / LSZH


0.6/1.0 (1.2) KV, Single Core Cable, Armoured, Sheathed CU / MGT / XLPE / LSZH / AWA / LSZH

Description :

Stranded copper conductor, Mica Glass tape & XLPE Insulated, Extruded LSZH bedding, Round Aluminium wire armoured and LSZH outer sheathed cable.

Core Colour   :   Natural - Sheath Colour  :  Black


Standards  :

Construction :  IEC 60502-1

Testing          :  BS 6387, BS EN / IEC 60754, BS EN / IEC 61034, IEC 60331, BS EN IEC 60332-3-24.

 

Installation Condition:

    * In free air or on a perforated cable tray

    * Ambient Air Temperature : 30°C

    * Conductor operating Temperature : 90°C

 

  • All conductors circular stranded or circular stranded compacted (class 2).
  • Cable construction to other standard and other core/sheath colour available upon request.

Cable Size Nominal Insulation Thickness  Approximate Diameter Approx. Cable Weight Standard Packing Length

(± 5%)

 

Maximum Conductor Resistance at 20°C

 

Current Rating
(3Ph AC)
Trefoil*

 

Over Conductor Under Armour

Over Armour

Overall

Sqmm  mm mm mm mm mm Kg/Km Meter Ohm/Km A
50 1.0 8.2 13.4 15.9 18.9 755 500 0.387 222
70 1.1 9.8 15.2 17.7 20.7 975 500 0.268 286
95 1.1 11.4 16.8 19.3 22.5 1260 500 0.193 346
120 1.2 12.8 18.4 21.6 25.0 1565 500 0.153 402
150 1.4 14.2 20.2 23.4 26.8 1875 500 0.124 463
185 1.6 15.9 22.3 25.5 29.1 2285 500 0.0991 529
240 1.7 18.5 25.1 28.3 32.1 2875 500 0.0754 625
300 1.8 20.6 27.4 30.6 34.4 3495 500 0.0601 720
400 2.0 23.3 30.9 34.9 39.1 4500 500 0.0470 815
500 2.2 26.5 34.5 38.5 42.9 5610 500 0.0366 918
630 2.4 30.0 38.4 42.4 47.0 7000 250 0.0283 1027