LSF Cable

Comparison between LSF & Non-LSF Cables

 

It is worth noting the similarities and differences between Non LSF Cables conforming to BS:5467, BS:6004, BS:6622 and LSF Cables

conforming to BS:6724, BS:7211, BS:7835.

 

Conductor Cross Sections / Specifications, thicknesses of various components, Dimensions and electrical parameters of a cables

conforming to BS:5467, BS:6004, BS:6622 (Non LSF Cable) and corresponding LSF cables conforming to BS:6724, BS:7211, BS:7835

are same. Moreover, during normal operations, behaviour of Non LSF Cable and corresponding LSF cables is exactally identical.

 

However, when assessed by the specified tests, relevant component of cables conforming to BS:6724, BS:7211, BS:7835 produce

lower levels of smoke and corrosive products under exposure to fire, compared to corresponding cables conforming to BS:5467,

BS:6004, BS:6622.

 

For better understanding of the above concept, let us take a specific example. 

Details

4x185 Sq.mm.

CU/XLPE/LSF/SWA/LSF to BS:6724

4x185 Sq.mm.

CU/XLPE/LSF/SWA/LSF to BS:6724

Coductor material Copper  Copper 
Nom.Thick. of insulation (mm) 1.6 1.6
Nom. Thick. Of extruded Bedding (mm) 1.4 1.4
Nom. Armour Wire Diameter (mm)  2.5 2.5
Nom. Thick. Of Outer Sheath (mm)  2.6 2.6
Approx. Overall Diameter (mm)    56.9   56.9
DC Resistance at 20° C (Ω/Km)        0.0991       0.0991
Current in Air (Amp) **  333 333
Volatge Drop (V/A/KM)   0.26  0.26
SC current of conductor for 1 Sec (KA)  25.9  25.9

 

 

** For installation conditions please refer refer Technical Information Section of this catalogue.

As apparent from the above tabulation, Conductor Cross Sections / Specifications, thicknesses of various components and Dimensions

and electrical parameters of both the above cables are identical.

However, when assessed by the specified tests, relevant component of cables conforming to BS:6724 produce lower levels of smoke

and corrosive products under exposure to fire. i.e. performance of cables conforming to BS:6724 is superiour under fire situations (as

depicted vide "Terminology"), where Non-LSF cables conforming to BS:5467 lack (as briefed vide "Introduction")