Low Voltage Cables/PVC Insulated Low Voltage Cables/Two Core Cables AL/PVC/PVC/SWA/PVC


Two Core Cables AL/PVC/PVC/SWA/PVC

600/1000 V - TWO CORE

ALUMINIUM CONDUCTOR
PVC INSULATED STEEL WIRE ARMOURED
PVC SHEATHED CABLE

(AL/PVC/PVC/SWA/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C  Thickness of Insulation  Thickness of Extruded Bedding Armour wire diameter Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross weight
Sqmm Ohm/Km mm mm mm mm mm Kg/Km Metre±10%   Kg
16 1.91 1.0 1.0 1.25 1.8 22.9 915 1000 D-14 1070
25 1.20 1.2 1.0 1.6 1.8 27.0 1330 500 D-12 775
35 0.868 1.2 1.0 1.6 1.8 29.2 1540 500 D-12 880
 
50 0.641 1.4 1.0 1.6 1.9 32.9 1680 500 D-16 1050
70 0.443 1.4 1.2 2.0 2.0 37.7 2300 500 D-18 1390
95 0.320 1.6 1.2 2.0 2.2 42.5 2790 500 D-18 1640
 
120 0.253 1.6 1.2 2.0 2.3 45.5 3150 500 D-19 1900
150 0.206 1.8 1.4 2.5 2.4 50.7 4060 500 D-19 2350
185 0.164 2.0 1.4 2.5 2.6 55.2 4710 250 D-18 1420
 
240 0.125 2.2 1.6 2.5 2.8 61.9 5700 250 D-18 1670
300 0.100 2.4 1.6 2.5 2.9 66.8 6530 250 D-19 1870
400 0.0778 2.6 1.6 2.5 3.2 74.3 7830 250 D-21 2380
 
500 0.0605 2.8 1.8 3.15 3.4 83.0 10170 200 D-22 2500

All conductors circular stranded or circular stranded compacted (Class 2).
All the Cables are insulated with either PVC Type 5 Heat Resisting 85°C compound and sheathed with PVC
Type 9/ST2 compound OR PVC type A/TI1 compound and sheathed with PVC type ST1/TM1 compound.
Cables conform to IEC 60502 - 1 and generally to BS 6346.