Rating Factors for variation in Thermal Resistivity of Soil for Three Single core Cables cables laid Direct in Ducts:

Nominal Area of Conductor mm²

Thermal Resistivity of Soil in K.m/W
  0.7  0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
50 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.73 0.69
70 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
95 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
120 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.72 0.67
150 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
185 1.13 1.10 1.07 1.04 1.0 0.93 0.86 0.79 0.75 0.70 0.67
240 1.14 1.11 1.07 1.04 1.0 0.93 0.86 0.79 0.74 0.70 0.66
300 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.79 0.74 0.69 0.65
400 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.65
500 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.64
630 1.15 1.12 1.09 1.05 1.0 0.93 0.84 0.78 0.72 0.68 0.64
800 1.16 1.12 1.09 1.05 1.0 0.93 0.84 0.77 0.72 0.67 0.64
1000 1.16 1.13 1.09 1.05 1.0 0.92 0.84 0.77 0.71 0.67 0.63